Delta

,

DPS Series UPS, Three Phase, 300/400/500/600/800/1000/1200 kVA

Categories: ,

The Next Generation UPS Answering the Demand of Large Data Centers and Colocations

Delta’s superior Ultron DPS series 300 – 1200kVA UPS supports unity output power factor to deliver up to 10 MW power capacity to meet the demands for large data centers and colocations that require higher power capacity. The Ultron DPS series guarantees the highest level of system reliability and resiliency by supporting self-detection of key components with pre-warning function, multilayered redundancy design, and complete power rating coverage. Moreover, the DPS series supports advanced manageability. Key environment parameters, and event analysis can all be monitored via local 10” LCD monitor and remotely. Along with optional battery management software, the DPS series enables users to achieve predictive maintenance and minimize system downtime, while lowering the total cost of ownership (TCO).

            Ultimate Availability

  • Supports up to 10 MW power capacity with the parallel redundancy and expansion up to 8 units
  • Redundancy components and dual CAN bus ensures system availability
  • Proactive detection of key component status for early diagnosis on UPS malfunction
  • Intelligent battery health diagnosis enables better battery maintenance and replacement
  • Advanced event analysis, including 10, 000 event logs, waveform capturing and key paremeters recording, to detect UPS abnomality and ensure higher availability
    Excellent Performance
  • The industry’s leading power density and smallest footprint with the design of both top/button cable entry and inbult switches, which allows you to flexibly utilize the space under the circumstance of high power requirements
  • Unity output power factor guarantees no-rating and provides 100% kW
  • AC-AC efficiency of up to 96.5% and 99% in ECO mode resulting in marked energy cost savings
  • Supports both VRLA and environment-friendly Li-ion batteries
    Sophisticated Manageability and Flexibility
  • User-friendly 10” color touch panel simplifies local UPS management
  • Environment information, such as security, water, fire, and temperature can be integrated and monitored via the LCD panel of the UPS
  • If the UPS is equipped with an external battery management system, the battery information can be integrated and monitored via the LCD panel of the UPS
  • Fully front access and modular design of key components shortens the mean time to repair (MTTR)
  • Flexible battery quantity of 30-46 pcs achieves optimal battery investment

Model         DPS-300K / DPS-400K / DPS-500K / DPS-600K
DPS-800K / DPS-1000K / DPS-1200K
Power Rating
● DPS-300K300 kVA / 300 kW
● DPS-400K400 kVA / 400 kW
● DPS-500K500 kVA / 500 kW
● DPS-600K600 kVA / 600 kW
● DPS-800K800 kVA / 800 kW
● DPS-1000K1000 kVA / 1000 kW
● DPS-1200K1200 kVA / 1200 kW
Input
Nominal Voltage220/380 V, 230/400 V, 240/415 V (3-phase, 4-wire + G)
Voltage Range176/304~276/478 VAC (full load)
Current Harmonic Distortion< 3% (with Full Linear Load) < 5% (with Full Non-linear Load) Power Factor> 0.99
Frequency Range40~70 Hz
Output
Voltage220/380 V, 230/400 V, 240/415 V (3-phase, 4-wire + G)
Voltage Harmonic Distortion< 1.5% (Linear Load) < 5% (Non-linear Load) Voltage Regulation± 1% (static), ± 5% (dynamic) Output Power Factor1 Frequency50/60 Hz (Auto-Selectable) Overload Capability≤ 125%: 10 min ≤ 150%: 1 min > 150%: 1 sec
Display10” Color Touch Panel
Interface
StandardRS232, Parallel port, USB, Modbus RS485, Input dry contact, Output dry contact, SNMP card inbuilt in touch screen
OptionalRelay I/O card, Battery cabinet temperature sensor cable
ConformanceSafety : CE
Efficiency
AC-AC ModeUp to 96.5%
ECO Mode99%
Battery
TypeVRLA, LiB
Charge Current
● DPS-300K90 A
● DPS-400K120 A
● DPS-500K150 A
● DPS-600K180 A
● DPS-800K240 A
● DPS-1000K300 A
● DPS-1200K360 A
Battery Quantity30–46 pcs
Environment
Operating Temperature0~40℃
Relative Humidity0~95% (non-condensing)
Audible Noise< 80 dB IP ProtectionIP20 Others Parallel Redundancy and ExpansionMaximum 8 units Emergency Power OffRemote and local Physical Dimensions (W x D x H) ● DPS-300K600* x 900 x 2000 mm ● DPS-400K/500K/600K1200* x 900 x 2000 mm ● DPS-800K1800 x 900 x 2000 mm ● DPS-1000K/1200K2450 x 900 x 2000 mm Weight ● DPS-300K515 kg ● DPS-400K700 kg ● DPS-500K811 kg ● DPS-600K970 kg ● DPS-800K1270 kg ● DPS-1000K1850 kg ● DPS-1200K2000 kg * The width is for the cabinet which has four inbuilt switches. All specifications are subject to change without prior notice.

 

 

 