HPH Series UPS, Three Phase, 160/200 kVA

Categories: ,
Highly reliable and efficient backup power for medium enterprise operations

The brand-new Ultron HPH series 160-200kVA is a true online double-conversion UPS offering the best-in-class combination of power performance and efficiency for medium data centers, pan-IT, and other mission critical applications. Thanks to Delta’s R&D expertise and excellent engineering capabilities, the Ultron HPH features up to 96.5% AC-AC efficiency, low iTHD < 3%, and high input power factor > 0.99 resulting in significant total cost of ownership (TCO) savings. Highlights of the highly reliable Ultron HPH series UPS design include key component redundancy and proactive battery health detection. With its combination of superior availability and power performance, the Ultron HPH 160-200kVA is the top choice for power protection of sustainable medium business operations.

Best-in-class Power Performance and Efficiency

  • High AC-AC efficiency of up to 96.5% and ECO mode to 99% for significant energy cost savings
  • Low harmonic pollution (iTHD < 3%) and high input power factor (> 0.99) reduces upstream investment costs

Assured Availability

  • Optional redundant controller supports dual CAN bus and ring connection for high system availability
  • Proactive battery aging detection for high reliability
  • Easy event log check via touch panel and firmware upgrade via USB port

Greater Flexibility

  • Parallel expansion and redundancy up to 8 units, 1.6MVA of total power capacity
  • Flexible battery configuration 30~46 pieces optimizes battery investment
  • Supports either top or bottom cable entry in the single cabinet. The unique fixed symmetric terminal design avoids cable bending issues to enhance cable reliability

Superior Manageability

  • User-friendly 10” colored LCD with touch panel enables easy local UPS management
  • Environment information such as security, water, fire and temperature can be integrated into the UPS for easy monitoring via the LCD of the UPS
  • If the UPS is equiped with Delta’s battery management system, the battery information can be integrated into the UPS and monitored via LCD

ModelHPH-160K / HPH-200K
Power Rating
● HPH-160K160 kVA* / 150 kW
● HPH-200K200 kVA / 200 kW
Input
Nominal Voltage220/380 Vac, 230/400 Vac, 240/415 Vac (3-phase, 4-wire + G)
Voltage Range176~276Vac (full load)
Current Harmonic Distortion≤ 3%**
Frequency40~70 Hz
Output
Voltage220/380 Vac, 230/400 Vac , 240/415 Vac (3-phase, 4-wire + G)
Voltage Harmonic Distortion≤ 0.5% (linear load)
Frequency50/60 Hz
Frequency Regulation± 0.05 Hz (battery mode)
Overload Capability≤ 125%: 10 minutes
≤ 150%: 1 minute
Display10” color touch screen
Interface
StandardRS232 x 1, Parallel port x 2, USB x 3, RS485 x 1, Relay I/O card slot x 1, REPO x 1, Input dry contact x 4, Output dry contact x 6,
Battery temperature sensor x 4, External switch detection x 4, RJ45 x 1, Ethernet x 1
OptionalRelay I/O card, Battery cabinet temperature sensor cable
Conformance
SafetyCE, RCM
UPS Classification According to IEC 62040-3VFI-SS-111
Efficiency
AC-AC ModeUp to 96.5%
ECO Mode99%
Battery
Nominal Voltage± 240 Vdc
Charge Voltage± 272 Vdc (adjustable from 204 V to 312 V)
Battery number configuration30~46 pcs (default: 40 pcs)
Environment
Operating Altitude1000 meters (without derating)
Operating Temperature0~40℃
Audible Noise< 70 dB Relative Humidity0~95% (non-condensing) Others Parallel Redundancy and ExpansionMaximum 8 units Remote Emergency Power OffYes Battery StartYes Physical Dimensions (W x D x H)600 x 1100 x 1600 mm Weight ● HPH-160K339 kg ● HPH-200K376 kg